Overview
Shielding does two jobs: it keeps outside interference out of the drive and encoder, and it keeps the drive's own emissions from bothering the equipment around it. This last part of the series covers shield termination, cabinet EMC, and picking a line filter.
Cable Shield Termination
How you terminate the shield is often what separates a clean system from one that's full of noise. Best case is a 360-degree circumferential clamp, either an EMC gland or a shield clamp:
- Use EMC cable glands with 360° shield contact
- Never use pigtail shield connections—they act as antennas above 1 MHz
- Terminate shields at both cable ends for motor and encoder cables
- For communication cables (RS-232), ground shield at one end only to prevent ground loops
Cabinet EMC Design
Treat the control cabinet as a Faraday cage. Every panel joint needs continuous electrical contact, and cable entries should go through EMC glands. Mount the EMI filter right at the entry point and keep its leads short, so there's as little unfiltered cable inside the cabinet as possible.
EMI Filter Selection
Put a line filter on the AC input to meet conducted emissions limits. Size it for the total current of every drive in the cabinet, and check that it's rated for the drives' PWM switching frequency, usually 16-20 kHz.